Answer
Feb 22, 2022 - 12:18 PM
We reached out to the manufacturer on this for their input and their response is below:
The unit is not capable of delivering 20 gpm, the maximum gpm through that unit is 10 gpm. It will take 02 units.
To achieve 150° at 20 gpm we would need to know what the incoming temperature is – we would also need to know what the application is – what are you heating the water for?
Likely that temperature rise with that flow rate will require you to pipe two units in parallel – that can be done but first we need the basics – what is the incoming water temperature.
For further assistance please email us direct at customerservice@prodryers.com and we can put you in touch with a specialist that can help. Thank you!